It seems that my floor heating is just a floor without the heating part at the moment. I have turned it on in the thermostats for every room 3 days ago already but I feel no heat coming from underneath the floor, except in the bathrooms, there I feel but only a little bit. Can also someone explain these. I know the ones above are the actuators and they are on since they have a red color, and the ones below are the control flow valves correct?
How can I adjust the flow for each room? Any help is appreciated
by Flimsy_Look7933
5 comments
Ask your landlord or Hauswart
The distributor with the red point should be warm. If not, either the pump is the problem or there is air in the system, preventing proper circulation. In either case, it’s a case for a specialist.
I have the same issue. Where exactly can I find those valves and pipes?
Don’t touch anything, call your landlord
Had that problem too a few years back. Two things broke: 3 actuators didn’t move/open anymore and the water circulation pump was dead. If the pipe to the actuators is warm then you should at least have water flowing. If not, check the pump (or boiler/heater).
Comments are closed.